| Applications | Machine tools, HVAC, Refrigeration, Water treatment, Process technology |
|---|---|
| Category | Electronic pressure switches |
| Accuracy at 25°C typ. | ± 0.5% FS typ. |
| Dielectric strength | 100 VAC, 50 Hz |
| Measurement principle | Thick film on ceramics |
| Vibration | 10 g (10 ... 2000 Hz) |
| NLH @ 25°C (BSL) typ. | ± 0.2% FS typ. |
| Pressure connections | G1 / 4 "f; G1 / 4" m; G1 / 2 "m, DIN3852-E; 1/4" NPT m; R1 / 4 "m, DIN3858; 7/16"-20UNF m, DIN3866; 7/16"-20UNF m, SAE4 (J1926); 7/16"-20UNF f, SAE J512, valve opener; G3 / 4 "frontal membrane |
| Media temperature | -25 ° C ... + 85 ° C |
| Shock | 50 g / 3 ms |
| Electrical connections | Plug M12x1, 5-pole; Plug male M12x1, 4-pole |
| Long-term stability 1 year type. | ± 0.3% FS typ. |
| Environment temperature |
-25 ° C ... + 85 ° C |
| Protection | IP67 |
| Output signal | 4 ... 20 mA, 0 ... 5 VDC, 1 ... 6 VDC, 0 ... 10 VDC, switchable mA or V |
| TEB typ. @ -25 ... + 85 ° C | ± 2.0% FS typ. |
| Measuring range | 0 ... 0.2 to 0 ... 100 bar 0 ... 2.5 to 0 ... 1500 psi adjustable |