| Max. pressure | 5000 Pa (50 mbar) |
|---|---|
| Pressure range | high adjustment accuracy due to individual laser-etched scale for each switch |
| Pressure range (adjustable) | 100…1000 Pa (1.0…10.0 mbar) |
| Switching capacity (Contact load) | 5 (0.8) A, 250 V AC 4 (0.7) A, 30 V DC |
| Contact | single-pole potential-free changeover contact, multi-layer contact, gold-plated (DDC compatible) |
| Media temperature | –30 …+85 °C |
| Operating Difference approx. | 0.4 mbar ± 15 % |
| Pressure connection | P1 (+) for higher pressure P2 (–) for lower pressure Ø 6.2 mm (nipples) |
| Electrical connection | 0.14 – 1.5 mm2, via terminal screws on circuit board |
| Housing | base: material PC (10 % GF), colour light grey (similar to RAL 7035), snap-on lid: material PC, transparent, cable gland PG 11 with strain relief |
| Membrane | silicone, LSR (Liquid Silicon Rubber, tempered at +200 °C, non-outgassing, LABS-free, no emission of varnish-adhesion inhibiting substances), long-term stability of switching points due to trapezoidal bead membranes |
| Humidity | < 90 % r. H., non-precipitating air |
| Mounting | by 4-hole base ring, plastic (included in the scope of delivery), recommended mounting position: vertical (pressure connections downward) – factory setting, horizontal (cap up/ down) |
| Protection class | II (according to EN 60 730) |
| Protection type | IP 54 with top cover (according to EN 60529) |
| Standards | CE conformity, low-voltage directive 2014/ 35/ EU |
| Tests | DVGW (according to DIN 1854), VDE 0630, EN 61058, directive on gas devices 2009/ 142/ EU, CE 0085 A P 0918 |
| Function | Contact 1 – 2 breaks when pressure/ differential pressure rises to the preset value. Contact 1 – 3 closes when pressure/ differential pressure drops and can be used as signal contact. |